Dikibi’s

//Dikibi’s

Dikibi’s

The inverter will be tested using a near ideal voltage supply set at 450 V.

The voltage output must be 240 V RMS single phase AC, within a +/12V band.

The frequency output must be 60 Hz single phase AC, within a band between 59.7 to 60.3 Hz.

Contact us regarding this product

Category:

Product Description

Voltage Input
The inverter will be tested using a near ideal voltage supply set at 450 V. This power supply will be floating. Its positive terminal will be connected to a 10 Ù wire wound resistor which will in turn be connected to the positive DC input terminal of the inverter. The voltage source will be very close to ripple free.
Voltage Output
The voltage output must be 240 V RMS single phase AC, within a +/12V band. After a transient change in the load the voltage should return to within acceptable bands in 0.1seconds or less and not leave the band again until the next load change. The voltage will be measured at the output of the inverter to ensure it remains within acceptable bands. Unintentional DC voltage limit: here must not be more than 1.2 volts DC present between the 2 AC terminals.
Frequency Output
The frequency output must be 60 Hz single phase AC, within a band between 59.7 to 60.3 Hz. After a transient change in the load the frequency, if it changes, should return to within the acceptable band in 0.1 seconds or less and not leave the band again until the next load change. The frequency will be measured at the output of the inverter to ensure it remains within acceptable bands.

Reviews

There are no reviews yet.

Be the first to review “Dikibi’s”